Friedrich SH20L30-A Manual de usuario

Busca en linea o descarga Manual de usuario para Acondicionadores de aire del sistema de división Friedrich SH20L30-A. Friedrich SH20L30-A User's Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir

Indice de contenidos

Pagina 1 - Service & Parts Manual

SH15L30-ASH20L30-ASH20L50-AHG-SVC-PRTS-05 (4-05)Service & Parts ManualRoom Air Conditioners50 & 60 Hz Models2005

Pagina 2 - TABLE OF CONTENTS

10NOTE:All inoperative compressors returned to Friedrich must have all lines properly plugged with the plugs from the replacement compressor.REFRIGERA

Pagina 3 - Performance Data: Cooling

11TROUBLESHOOTINGPROBLEM POSSIBLE CAUSE TO CORRECTUNIT DOES NOT RUN.Power disconnected. Check power source.System switch in “Off” position.Set switch

Pagina 4 - FIGURE 1 INTERNAL OVERLOAD

12TROUBLESHOOTING (Continued)PROBLEM POSSIBLE CAUSE TO CORRECTCOMPRESSOR ATTEMPTS TO START, OR RUNS FOR SHORT PERIODS ONLY. CYCLES ON OVERLOAD.Compr

Pagina 5 - Load side

13TROUBLESHOOTING (Continued)PROBLEM POSSIBLE CAUSE TO CORRECTFAN MOTOR DOES NOT RUN.Defective switch (On-Off). Check continuity across terminals 2 a

Pagina 6 - FIGURE 6 SWITCH, ON-OFF

14WIRING DIAGRAMMODELS SH15L30-A, SH20L30-A, SH20L50-A

Pagina 7

15HAZARDGARD CABINET PARTS

Pagina 8 - SEALED REFRIGERATION SYSTEM

16HAZARDGARD CHASSIS PARTS

Pagina 9 - COMPRESSOR MOTOR BURNOUT

17HAZARDGARD PARTS LIST REF DESCRIPTION PART NO# MODELS CODEELECTRICAL PARTSSH15L30-ASH20L30-ASH20L50-A1 COMPRESSOR 61193549 1 6001 COMPRESSOR 611935

Pagina 10 - TROUBLESHOOTING AND SERVICE

18REF DESCRIPTION PART NO# MODELS CODECHASSIS PARTSSH15L30-ASH20L30-ASH20L50-A26 SHROUD, CONDENSER 61803601 172026 SHROUD, CONDENSER 61804901 1172027

Pagina 12 - TROUBLESHOOTING (Continued)

2TABLE OF CONTENTS Specifi cations ...

Pagina 13

HG-SVC-PRTS-05 (4-05)Use Factory Certifi ed Parts.FRIEDRICH AIR CONDITIONING CO.Post Office Box 1540 · San Antonio, Texas 78295-15404200 N. Pan Am Expr

Pagina 14 - WIRING DIAGRAM

3EVAPORATOR AIR TEMP. DEG. FEVAPORATOR TEMP. DEG. FCONDENSER TEMP.DEG. FDischarge TempSuction TempLiquid TempSuper HeatSub-CoolingOPERATING PRESSURESE

Pagina 15 - HAZARDGARD CABINET PARTS

4COMPRESSOR WINDING TEST (Figure 2.)Remove the compressor terminal box cover and disconnect the wires from the terminals. Using an ohmmeter, check con

Pagina 16 - HAZARDGARD CHASSIS PARTS

5FAN MOTOR (Figure 4)A 230 volt single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A running capa

Pagina 17 - HAZARDGARD PARTS LIST

6RED DOTRUN CAPACITORFANMOTORCOMPRESSORFIGURE 7 RUN CAPACITOR HOOK–UPCAPACITOR, RUNA run capacitor is wired across the auxiliary and main winding o

Pagina 18

7Note: The temperature must be within the range listed to check the thermostat. Refer to the troubleshooting section in this manual for additional i

Pagina 19

8LOW AMBIENT BYPASS VALVE (Figure 9)The HazardGard unit is designed to operate at low outside ambient temperatures. This is accomplished by the use o

Pagina 20 - Use Factory Certifi ed Parts

9 NOTE: This procedure can be sped up by the use of heat lamps, or by breaking the vacuum with refrigerant or dry nitrogen at 5,000 microns. Pressure